Validation of a Switching Operation in the External Grid of Gunfleet Sand Offshore Wind Farm by Means of EMT Simulations

Iván Arana Aristi, J. Okholm, Joachim Holbøll

Research output: Chapter in Book/Report/Conference proceedingArticle in proceedingsResearchpeer-review

102 Downloads (Pure)

Abstract

This paper presents the voltage signals occurring during a switching operation recorded in the external grid of Gunfleet Sands Offshore Wind Farm recorded with an Elspec measurement system. The measurements are compared to electromagnetic (EMT) simulations for validation of the wind farm model using PSCAD/EMTDC. The simulation model then was modified to investigate the influence of a capacitor bank connection. It was found that for this kind of transients, the amount of wind turbines (wind turbine transformers, high frequency filters and wind turbine converter) included in the model makes a difference to the results; while the cable models (PI or distributed) and the type of model of the wind turbines converter (voltage source or open end), does not have a considerable influence on the transient response at the PCC or MV terminals of the park transformers
Original languageEnglish
Title of host publication10th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as on Transmission Networks for Offshore Wind Farms : Proceedings
Publication date2011
ISBN (Print)978-3-9813870-3-2
Publication statusPublished - 2011
Event10th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as on Transmission Networks for Offshore Wind Farms - Aarhus, Denmark
Duration: 25 Oct 201126 Oct 2011
http://www.windintegrationworkshop.org/aarhus2011/index.html

Workshop

Workshop10th International Workshop on Large-Scale Integration of Wind Power into Power Systems as well as on Transmission Networks for Offshore Wind Farms
CountryDenmark
CityAarhus
Period25/10/201126/10/2011
Internet address

Keywords

  • Wind farm
  • EMT simulations and transient overvoltages
  • Capacitor bank