Use of visual CO2 feedback as a retrofit solution for improving classroom air quality

Pawel Wargocki, Nuno Alexandre Faria Da Silva

    Research output: Contribution to journalJournal articleResearchpeer-review

    Abstract

    Carbon dioxide (CO2) sensors that provide a visual indication were installed in classrooms during normal school operation. During 2-week periods, teachers and students were instructed to open the windows in response to the visual CO2 feedback in 1week and open them, as they would normally do, without visual feedback, in the other week. In the heating season, two pairs of classrooms were monitored, one pair naturally and the other pair mechanically ventilated. In the cooling season, two pairs of naturally ventilated classrooms were monitored, one pair with split cooling in operation and the other pair with no cooling. Classrooms were matched by grade. Providing visual CO2 feedback reduced CO2 levels, as more windows were opened in this condition. This increased energy use for heating and reduced the cooling requirement in summertime. Split cooling reduced the frequency of window opening only when no visual CO2 feedback was present.
    Original languageEnglish
    JournalIndoor Air
    Volume25
    Issue number1
    Pages (from-to)105-114
    Number of pages10
    ISSN0905-6947
    DOIs
    Publication statusPublished - 2015

    Keywords

    • Schools
    • Classrooms
    • Carbon dioxide
    • Ventilation
    • Retrofit solution
    • Energy
    • Indoor air quality