T1 - Theoretical analysis of the performance of different cooling strategies with the concept of cool exergy
AU - Kazanci, Ongun Berk
AU - Shukuya, Masanori
AU - Olesen, Bjarne W.
PY - 2016
Y1 - 2016
N2 - The whole chains of exergy flows for different cooling systems were compared. The effects of cooling demand
(internal vs. external solar shading), space cooling method (floor cooling vs. air cooling with ventilation system),
and the availability of a nearby natural heat sink (intake air for the ventilation system being outdoor air vs. air
from the crawl-space, and air-to-water heat pump vs. ground heat exchanger as cooling source) on system exergy
performance were investigated.
It is crucial to minimize the cooling demand because it is possible to use a wide range of heat sinks (ground,
lake, sea-water, etc.) and indoor terminal units, only with a minimized demand. The water-based floor cooling
system performed better than the air-based cooling system; when an air-to-water heat pump was used as the cooling source, the required exergy input was 28% smaller for the floor cooling system. The auxiliary exergy
input of air-based systems was significantly larger than the water-based systems.
The use of available cool exergy in the crawl-space resulted in 54% and 29% smaller exergy input to the power
plant for the air-based and water-based cooling systems, respectively. For floor cooling, the exergy input to the
power plant can be reduced by 90% and 93%, with the use of ground, and use of the ground and the air in the
crawl-space, respectively. A new approach to exergy efficiency was introduced and used to prove that the exergy
supply from the ground matches well with the low exergy demand of the floor cooling system.
AB - The whole chains of exergy flows for different cooling systems were compared. The effects of cooling demand
(internal vs. external solar shading), space cooling method (floor cooling vs. air cooling with ventilation system),
and the availability of a nearby natural heat sink (intake air for the ventilation system being outdoor air vs. air
from the crawl-space, and air-to-water heat pump vs. ground heat exchanger as cooling source) on system exergy
performance were investigated.
It is crucial to minimize the cooling demand because it is possible to use a wide range of heat sinks (ground,
lake, sea-water, etc.) and indoor terminal units, only with a minimized demand. The water-based floor cooling
system performed better than the air-based cooling system; when an air-to-water heat pump was used as the cooling source, the required exergy input was 28% smaller for the floor cooling system. The auxiliary exergy
input of air-based systems was significantly larger than the water-based systems.
The use of available cool exergy in the crawl-space resulted in 54% and 29% smaller exergy input to the power
plant for the air-based and water-based cooling systems, respectively. For floor cooling, the exergy input to the
power plant can be reduced by 90% and 93%, with the use of ground, and use of the ground and the air in the
crawl-space, respectively. A new approach to exergy efficiency was introduced and used to prove that the exergy
supply from the ground matches well with the low exergy demand of the floor cooling system.
U2 - 10.1016/j.buildenv.2016.02.013
DO - 10.1016/j.buildenv.2016.02.013
M3 - Journal article
SN - 0360-1323
VL - 100
SP - 102
EP - 113
JO - Building and Environment
JF - Building and Environment