@book{15efd3302df347edb41b4dc60333c0ec,
title = "Simulation of interaction between wind farm and power system",
abstract = "A dynamic model of the wind farm Hagesholm has been implemented in the dedicated power system simulation program DIgSILENT. The wind farm con- sists of six 2MW NM2000/72 wind turbines from NEG-Micon. The model has been verified using simultaneous powerquality measurements on the 10 kV terminals of a single wind turbine and power performance measurements on two wind turbines. The verification shows a generally good agreement between simulations and measurements, although the simulations at higher windspeeds seem to underestimate the power and voltage fluctuations. A way to improve the simulation at higher wind speeds is suggested.",
keywords = "1-E vind, Ris{\o}-R-1281, Ris{\o}-R-1281(EN)",
author = "S{\o}rensen, {Poul Ejnar} and Hansen, {Anca Daniela} and L. Janosi and J. Bech and B. Bak-Jensen",
year = "2002",
language = "English",
isbn = "87-550-2912-4",
series = "Denmark. Forskningscenter Risoe. Risoe-R",
number = "1281(EN)",
}