Skip to main navigation Skip to search Skip to main content

Sensory pollution and microbial contamination of ventilation filters

  • Jan H. Pejtersen

    Research output: Contribution to journalJournal articleResearchpeer-review

    Abstract

    The sensory pollution load and microbial contamination of glass-fibre filters at high and low relative humidity were investigated in an experimental set-up in the laboratory. Dust and particles from the outdoor air were collected in two EU7 glass-fibre filters for a pre-conditioning period of 16-18 weeks during which there was a constant airflow with a velocity of 1.9 m/s through the filters. One of the filters was exposed to outdoor air of approximately 40% relative humidity and 10°C, the other to outdoor air of approximately 80% relative humidity and 5°C. The dust in ventilation filters can constitute a serious pollution source in the indoor environment, causing deterioration in the quality of the supply air even before it enters the ventilated spaces. The sensory pollution load from the used filters after the continuous operating time of 16-18 weeks was significantly higher than the sensory pollution load from new filters but the sensory load at 40% and 80% relative humidity did not differ. The microbial contamination of the supply air downstream of the filters, which on average had been exposed to outdoor air of 40% and 80% relative humidity, was negligible.
    Original languageEnglish
    JournalIndoor Air
    Volume6
    Issue number4
    Pages (from-to)239-248
    ISSN0905-6947
    DOIs
    Publication statusPublished - 1996

    Fingerprint

    Dive into the research topics of 'Sensory pollution and microbial contamination of ventilation filters'. Together they form a unique fingerprint.

    Cite this