Skip to main navigation Skip to search Skip to main content

Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols

  • Benjamin Jones*
  • , Christopher Iddon
  • , Marwa Zaatari
  • , Pawel Wargocki
  • , Richard Bruns
  • *Corresponding author for this work
  • University of Nottingham
  • University College London
  • DZINE
  • Johns Hopkins Bloomberg School of Public Health

Research output: Contribution to journal › Journal article › Research › peer-review

209 Downloads (Orbit)

Abstract

This paper describes the risk assessment modeling used to establish airflow requirements in ASHRAE Standard 241 (2023) – Control of Infectious Aerosols. The standard sets minimum equivalent clean airflow rates per person (ECAi) to reduce long-range airborne disease transmission indoors during high infection risk periods. These requirements cover buildings and occupancy categories such as correctional facilities, schools, healthcare facilities, commercial spaces, and residences.

The modeling employs the Wells–Riley infection risk model to estimate infection probability from inhaling aerosols over one hour. A probabilistic approach accounts for uncertainties, especially in key parameters like viral load, which can vary widely. Input parameters are based on SARS-CoV-2 data, as it was the primary motivation for the standard and provides higher-quality data.

ECAi values are set to achieve a 0.1% hourly infection probability 96% of the time across different occupancy categories, resulting in ECAi values between 10-45 L s−1 per person. The standard focuses on long-range transmission and serves as one protective layer, complementing vaccines and personal protective equipment. 

Uncertainties are significant so the ECAi values represent informed estimates rather than precise values. This risk-based method provides a rational approach for setting minimum airflow requirements to mitigate airborne infection risks during outbreaks.
Original languageEnglish
Article number113318
JournalBuilding and Environment
Volume283
Number of pages11
ISSN0360-1323
DOIs
Publication statusPublished - 2025

UN SDGs

This output contributes to the following UN Sustainable Development Goals (SDGs)

  1. SDG 3 - Good Health and Well-being
    SDG 3 Good Health and Well-being

Keywords

  • Transmission risk
  • Ventilation
  • Airborne
  • SARS-CoV-2
  • COVID-19
  • Quantifying quanta

Fingerprint

Dive into the research topics of 'Risk modeling for ASHRAE Standard 241-2023 — Control of infectious aerosols'. Together they form a unique fingerprint.

Cite this