Abstract
valuating the thermal performance of facade BIPV components in practical
engineering applications remains a challenge. To quantify the impact of
their thermal effects, this study proposes the equivalent additional
thermal resistance (ΔRBIPV) and the equivalent heat transfer coefficient (KBIPV), together with their calculation methods. The differences in ΔRBIPV
among five climate zones in China, including the severe cold zone, cold
zone, hot summer and cold winter zone, hot summer and warm winter zone,
and mild climate zone, are systematically analyzed. The KBIPV
values for the five climate zones are further compared with the
corresponding limits of external wall heat transfer coefficients (Klimit)
specified in the building thermal code, and based on this comparison,
strategies for reducing external wall insulation thickness are proposed.
The results indicate that the annual average ΔRBIPV values for the five climate zones are 1.07, 1.01, 0.98, 0.97, and 1.03 m2 K/W,
respectively. With the application of facade BIPV components, the
insulation thickness of external walls in Zone I and II can be reduced
by 42 mm and 39 mm, respectively, while no additional insulation layer
is required for Zone III, IV, and V.
| Original language | English |
|---|---|
| Article number | 125336 |
| Journal | Renewable Energy |
| Volume | 262 |
| Number of pages | 17 |
| ISSN | 0960-1481 |
| DOIs | |
| Publication status | Published - 2026 |
Keywords
- Calculation method
- Differences among climate zones
- Equivalent additional thermal resistance (ΔR BIPV)
- Equivalent heat transfer coefficient (K BIPV)
- Facade BIPV component
- Insulation thickness optimization strategy