On the Response of Interleaved Transformer Windings to Surge Voltages

Research output: Contribution to journalJournal article – Annual report year: 1971Researchpeer-review

  • Author: Pedersen, A.

    Technical University of Denmark

View graph of relations

The high series capacitance theory for the response of interleaved transformer windings to surge voltages is criticized from the point of view that an increased series capacitance as a result of interleaving is incompatible with the concept of a pure capacitive initial voltage distribution. A new theory is proposed according to which the distributed earth capacitances are charged up during an initial period by heavy currents flowing into the winding through surge impedances formed by the coils as a result of interleaving. Formulas are derived for the initial voltage distribution and for the maximum axial voltage gradient
Original languageEnglish
JournalI E E E Transactions on Power Systems
Volume82
Issue number66
Pages (from-to)349-356
ISSN0885-8950
DOIs
Publication statusPublished - 1963

Bibliographical note

Copyright: 1963 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE

CitationsWeb of Science® Times Cited: No match on DOI

Download statistics

No data available

ID: 3597888