Modelling of a thermally activated building system (TABS) combined with free-hanging acoustic ceiling units using computational fluid dynamics (CFD)

Luis Marcos Domínguez Lacarte, Jianhua Fan*

*Corresponding author for this work

Research output: Contribution to journalJournal articleResearchpeer-review

1 Downloads (Pure)

Abstract

Thermally Activated Building Systems (TABS) have proven to be an energy-efficient solution to achieve optimal indoor thermal environment in buildings. This solution uses the building mass to store heat and by means of water pipes embedded in the concrete slabs adjust the temperature in the premises. The active surfaces of TABS need to be as exposed as possible, but exposing bare
concrete surfaces has a negative impact on the acoustic quality in the premises. Acoustic solutions capable of providing optimal acoustic comfort while allowing the heat exchange between the TABS and the room are desirable. This study focuses on the influence of two types of free-hanging ceiling absorbers (horizontal and vertical) on the cooling performance of the TABS. Different scenarios are investigated for each type of sound absorber. Computational Fluid Dynamics (CFD) simulations are used to illuminate the nature of the heat exchange between the TABS and the room and the occupants. The simulations are validated by comparison with full scale measurements in laboratory conditions. The study shows that for equivalent sound absorption levels, free-hanging vertical sound absorbers have a lower impact on the heat exchange between the room and the TABS compared to free-hanging horizontal sound absorbers. Cold air stagnation between the sound absorber units and the TABS has been identified as the major cause of the cooling performance decrease of the TABS.
Original languageEnglish
JournalBuilding Simulation
Volume11
Issue number2
Pages (from-to)315-324
ISSN1996-3599
DOIs
Publication statusPublished - 2018

Keywords

  • TABS
  • Thermal environment
  • Sound absorption
  • Cooling capacity
  • Full-scale measurements
  • Building simulations
  • Computational fluid dynamics

Cite this

@article{a401b8dbb813478ba7a750a51756d05e,
title = "Modelling of a thermally activated building system (TABS) combined with free-hanging acoustic ceiling units using computational fluid dynamics (CFD)",
abstract = "Thermally Activated Building Systems (TABS) have proven to be an energy-efficient solution to achieve optimal indoor thermal environment in buildings. This solution uses the building mass to store heat and by means of water pipes embedded in the concrete slabs adjust the temperature in the premises. The active surfaces of TABS need to be as exposed as possible, but exposing bareconcrete surfaces has a negative impact on the acoustic quality in the premises. Acoustic solutions capable of providing optimal acoustic comfort while allowing the heat exchange between the TABS and the room are desirable. This study focuses on the influence of two types of free-hanging ceiling absorbers (horizontal and vertical) on the cooling performance of the TABS. Different scenarios are investigated for each type of sound absorber. Computational Fluid Dynamics (CFD) simulations are used to illuminate the nature of the heat exchange between the TABS and the room and the occupants. The simulations are validated by comparison with full scale measurements in laboratory conditions. The study shows that for equivalent sound absorption levels, free-hanging vertical sound absorbers have a lower impact on the heat exchange between the room and the TABS compared to free-hanging horizontal sound absorbers. Cold air stagnation between the sound absorber units and the TABS has been identified as the major cause of the cooling performance decrease of the TABS.",
keywords = "TABS, Thermal environment, Sound absorption, Cooling capacity, Full-scale measurements, Building simulations , Computational fluid dynamics",
author = "Lacarte, {Luis Marcos Dom{\'i}nguez} and Jianhua Fan",
year = "2018",
doi = "10.1007/s12273-017-0392-x",
language = "English",
volume = "11",
pages = "315--324",
journal = "Building Simulation",
issn = "1996-3599",
publisher = "Tsinghua University Press",
number = "2",

}

Modelling of a thermally activated building system (TABS) combined with free-hanging acoustic ceiling units using computational fluid dynamics (CFD). / Lacarte, Luis Marcos Domínguez ; Fan, Jianhua.

In: Building Simulation, Vol. 11, No. 2, 2018, p. 315-324.

Research output: Contribution to journalJournal articleResearchpeer-review

TY - JOUR

T1 - Modelling of a thermally activated building system (TABS) combined with free-hanging acoustic ceiling units using computational fluid dynamics (CFD)

AU - Lacarte, Luis Marcos Domínguez

AU - Fan, Jianhua

PY - 2018

Y1 - 2018

N2 - Thermally Activated Building Systems (TABS) have proven to be an energy-efficient solution to achieve optimal indoor thermal environment in buildings. This solution uses the building mass to store heat and by means of water pipes embedded in the concrete slabs adjust the temperature in the premises. The active surfaces of TABS need to be as exposed as possible, but exposing bareconcrete surfaces has a negative impact on the acoustic quality in the premises. Acoustic solutions capable of providing optimal acoustic comfort while allowing the heat exchange between the TABS and the room are desirable. This study focuses on the influence of two types of free-hanging ceiling absorbers (horizontal and vertical) on the cooling performance of the TABS. Different scenarios are investigated for each type of sound absorber. Computational Fluid Dynamics (CFD) simulations are used to illuminate the nature of the heat exchange between the TABS and the room and the occupants. The simulations are validated by comparison with full scale measurements in laboratory conditions. The study shows that for equivalent sound absorption levels, free-hanging vertical sound absorbers have a lower impact on the heat exchange between the room and the TABS compared to free-hanging horizontal sound absorbers. Cold air stagnation between the sound absorber units and the TABS has been identified as the major cause of the cooling performance decrease of the TABS.

AB - Thermally Activated Building Systems (TABS) have proven to be an energy-efficient solution to achieve optimal indoor thermal environment in buildings. This solution uses the building mass to store heat and by means of water pipes embedded in the concrete slabs adjust the temperature in the premises. The active surfaces of TABS need to be as exposed as possible, but exposing bareconcrete surfaces has a negative impact on the acoustic quality in the premises. Acoustic solutions capable of providing optimal acoustic comfort while allowing the heat exchange between the TABS and the room are desirable. This study focuses on the influence of two types of free-hanging ceiling absorbers (horizontal and vertical) on the cooling performance of the TABS. Different scenarios are investigated for each type of sound absorber. Computational Fluid Dynamics (CFD) simulations are used to illuminate the nature of the heat exchange between the TABS and the room and the occupants. The simulations are validated by comparison with full scale measurements in laboratory conditions. The study shows that for equivalent sound absorption levels, free-hanging vertical sound absorbers have a lower impact on the heat exchange between the room and the TABS compared to free-hanging horizontal sound absorbers. Cold air stagnation between the sound absorber units and the TABS has been identified as the major cause of the cooling performance decrease of the TABS.

KW - TABS

KW - Thermal environment

KW - Sound absorption

KW - Cooling capacity

KW - Full-scale measurements

KW - Building simulations

KW - Computational fluid dynamics

U2 - 10.1007/s12273-017-0392-x

DO - 10.1007/s12273-017-0392-x

M3 - Journal article

VL - 11

SP - 315

EP - 324

JO - Building Simulation

JF - Building Simulation

SN - 1996-3599

IS - 2

ER -