Three different glazings have been investigated in the Danish
experimental setup METSET. (A device for calorimetric measurement
of total solar energy transmittance - g-value).The purpose of the
measurements is to increase the confidence in the calorimetric
measurements. This is done by comparison between measurements and
calculations. For the investigated types of glazings the g-value
can be found with high accuracy by calculations if the relevant
optical and thermal data are available. Therefor the calculation
results are considered as reference results. The measurements are
carried out under different boundary conditions than the reference
conditions. The correction from experimental to reference
conditions is carried by using a physical model corresponding to
the model described in EN410 and ISO9050. The measured results are
in general in good agreement with the calculated results (maximum
difference is 4.4%). This gives good reason to increase the
confidence in the method used to obtain the measured g-values.
Number of pages | 15 |
---|
Publication status | Published - 1998 |
---|