Abstract
The mean velocity in rooms predicted by CFD simulations based on RANS equations differs from the mean (in time) magnitude of the velocity, i.e. the mean speed, in rooms measured by low velocity thermal anemometers with omnidirectional sensor. This discrepancy results in incorrect thermal comfort assessment by the CFD predictions as well as incorrect validation of the predicted velocity field. In this paper the discrepancies are discussed and identified, and a method for estimating of the mean speed based on the CFD predictions of mean velocity and kinetic turbulence energy is suggested. The method is applied and improvement in thermal comfort assessment is demonstrated.
| Original language | English |
|---|---|
| Title of host publication | Procedings of Roomvent 2004 |
| Volume | CD Rom |
| Place of Publication | Portugal |
| Publisher | University of Coimbra |
| Publication date | 2004 |
| Publication status | Published - 2004 |
| Event | 9th International Conference on Air Distribution in Rooms - University of Coimbra, Coimbra, Portugal Duration: 5 Sept 2004 → 8 Sept 2004 Conference number: 9 |
Conference
| Conference | 9th International Conference on Air Distribution in Rooms |
|---|---|
| Number | 9 |
| Location | University of Coimbra |
| Country/Territory | Portugal |
| City | Coimbra |
| Period | 05/09/2004 → 08/09/2004 |
Fingerprint