Improved control of radiator heating systems with thermostatic radiator valves without pre-setting function

Theofanis Benakopoulos, Robbe Salenbien, Dirk Vanhoudt, Svend Svendsen

    Research output: Contribution to journalJournal articleResearchpeer-review

    289 Downloads (Pure)

    Abstract

    Low-temperature district heating will play an important role in a future free of fossil fuels. This will only be able to be realized through the low-temperature operation of heating systems in existing buildings. Existing radiator systems can operate with low temperatures for most of the year because they are designed for extremely cold days, but errors have to be corrected and the control of the radiator systems needs to be improved. In this paper, we present a strategy to achieve low-temperature operation from the radiator system of a multi-family building in Denmark without a pre-setting function in the thermostatic radiator valves. The strategy is based on operating the system with a combination of a minimum supply temperature and small temperature differences over the radiators. The operation of the system is analyzed through a thermal-hydraulic model. A minimum supply temperature weather compensation curve was calculated and implemented in the central supply temperature control. Return temperature measurements in the substation, the risers, and several critical radiators were performed before and after the implementation of the strategy. The measurements confirm that a lower supply temperature results in a reduction of the return temperature. However, the system operator needs to be supported by a tool package to correctly maintain the system’s operation.
    Original languageEnglish
    Article number3215
    JournalEnergies
    Volume12
    Issue number17
    Number of pages24
    ISSN1996-1073
    DOIs
    Publication statusPublished - 2019

    Keywords

    • Low-temperature district heating
    • Radiator heating system
    • Thermostatic radiator valves
    • Low-temperature operation
    • Low supply temperature
    • Multi-family building
    • Thermal-hydraulic model
    • Return temperature measurements