Field measurements of perceived air quality and concentration of volatile organic compounds in four offices of the university building

    • Czech Technical University in Prague
    • European Commission

    Research output: Contribution to journal › Journal article › Research › peer-review

    Abstract

    Field measurements of perceived air quality were conducted in four refurbished offices at the Czech Technical University in Prague. The offices were refurbished as part of the research project Clear-up to serve as a field test facility. The present paper describes measurements conducted to investigate the perceived air quality, sensory pollution load and concentration of Volatile Organic Compounds (VOCs) in the offices. As the refurbishment comprised also installation of demand controlled ventilation (DCV), its influence on the perceived air quality was also tested. Measurements comprised the assessments of perceived air quality and objective measurements of operative temperature, relative humidity, CO2 and VOCs concentrations. Results showed that the mean sensory pollution load in unoccupied offices was 0.09 ± 0.01 olf/m2 (mean ± SEM). This falls into the category of a low-polluting building according to CEN Report CR 1752. The acceptability of the air quality was worst in unoccupied offices ventilated with minimum air change rate (0.4 h-1). Application of DCV decreased the CO2 concentration, but did not result in statistically significant improvement of perceived air quality.
    Original languageEnglish
    Article number1048-1058
    JournalIndoor and Built Environment
    Pages (from-to)24
    Number of pages8
    ISSN1420-326X
    DOIs
    Publication statusPublished - 2015

    Fingerprint

    Dive into the research topics of 'Field measurements of perceived air quality and concentration of volatile organic compounds in four offices of the university building'. Together they form a unique fingerprint.

    Cite this