Abstract
This paper deals with transient conditions in the collection grid of offshore wind farms under different faults. A model of a standard wind farm was established in two versions, with a floating and a grounded collection grid respectively. Line to ground faults and three-phase to ground faults were applied at critical points at worst-case phase angle and the results compared. The simulations show that it is better with a grounded collection grid, since lack of a ground reference will prevent the system from recovering after a line to ground fault.
Original language | English |
---|---|
Title of host publication | 2008 Annual IEEE Student Paper Conference : AISPC08 |
Publisher | IEEE Computer Society Press |
Publication date | 2008 |
Pages | 1-5 |
ISBN (Print) | 9781424421565 |
DOIs | |
Publication status | Published - 2008 |
Event | 2008 Annual IEEE Student Paper Conference - Aalborg, Denmark Duration: 15 Feb 2008 → 26 Feb 2008 Conference number: 2 https://ieeexplore.ieee.org/xpl/conhome/4460535/proceeding |