Abstract
Thermo Active Building Systems (TABS), described as radiant heating or cooling systems with pipes embedded in the building structure, represent a sustainable alternative to replace conventional systems by using source temperatures close to room temperatures. The use of suspended ceiling in office buildings to cover acoustic requirements hinders the use of TABS. To measure the reduction of
the heat capacity, several experiments are performed in a room equipped with TABS in the upper deck and mixing ventilation. The heat transfer is measured for different suspended ceiling covering percentages, occupancy scenarios and ventilation rates. The gained results indicate that the heat capacity coefficient of the ceiling surface is reduced by around 30% when the suspended ceiling
covering is 70% of the total ceiling area, and 45% when the covering area is up to 87%. The results also demonstrate that the ventilation rate has a high influence on the convective heat capacity. When the ventilation rate is increased from 1.7 h-1 to 2.9 h-1, the heat transfer coefficient increases up to 16% for the same occupancy and suspended ceiling layout.
| Original language | English |
|---|---|
| Title of host publication | Proceedings of the 10th Nordic Symposium on Building Physics |
| Editors | Jesper Arfvidsson, Lars-Erik Harderup, Anders Kumlin, Bitte Rosencrantz |
| Number of pages | 8 |
| Publisher | Lund University |
| Publication date | 2014 |
| Pages | 735-741 |
| Article number | 91 |
| ISBN (Electronic) | 978-91-88722-53-9 |
| Publication status | Published - 2014 |
| Event | 10th Nordic Symposium on Building Physics - Lund, Sweden Duration: 15 Jun 2014 → 19 Jun 2014 Conference number: 10 http://www.nsb2014.se/ |
Conference
| Conference | 10th Nordic Symposium on Building Physics |
|---|---|
| Number | 10 |
| Country/Territory | Sweden |
| City | Lund |
| Period | 15/06/2014 → 19/06/2014 |
| Internet address |
Keywords
- Thermo active building systems
- Suspended ceilings
- Heat capacity