Comparison of a CO2 refrigeration and heat pump test system with and without ejector

Martin R. Kærn, Yulong Song, Wiebke B. Markussen, Brian Elmegaard

    Research output: Chapter in Book/Report/Conference proceedingArticle in proceedingsResearchpeer-review

    184 Downloads (Pure)

    Abstract

    This experimental study investigates the performance and some questions related to controllability of a small-scale CO2 ejector test system. The test system is operated in both refrigeration and heat pump operation with and without the ejector. Different inlet temperatures on the secondary side of the gas cooler are investigated for both operations as well as a variation of compressor speed.
    Additionally, the possibility to flood the evaporator in ejector mode is studied including the use of a prototype “quality sensorTM” (capacitive void fraction sensor). The results showed that the ejector performed well in refrigeration operation, considering the pressure drop caused by the undersized piping from the diffuser to the suction of the compressor.
    The COP improved by around 0.2 (12 % to 17 %) and if the superheat (10 K) was eliminated by flooding the evaporator, a further 0.3 improvement was possible (33 % compared with standard cycle mode). In heat pump operation, the COP became similar or lower because the ejector was slightly oversized for that operation (gas cooler pressure became lower than optimal).
    The quality sensor showed a significant change in the electrical capacitance as the evaporator was increasingly flooded. Furthermore, the measured capacitances were converted into reasonable void fractions by using both a linear calibration function and an annular flow void fraction calibration function from the literature.
    The gas cooler pressure was possible to control with the speed of the compressor within a range of around 10 bar in refrigeration mode, but had insignificant effect on the gas cooler pressure in heat pump mode.
    Original languageEnglish
    Title of host publicationProceedings of the13th IIR-Gustav Lorentzen Conference on Natural Refrigerants
    PublisherInternational Institute of Refrigeration
    Publication date2018
    Pages847-855
    Article number1290
    ISBN (Electronic)9782362150265
    DOIs
    Publication statusPublished - 2018
    Event13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018) - Valencia, Spain
    Duration: 18 Jun 201820 Jun 2018

    Conference

    Conference13th IIR Gustav Lorentzen Conference on Natural Refrigerants (GL2018)
    Country/TerritorySpain
    CityValencia
    Period18/06/201820/06/2018
    SeriesScience et Technique du Froid
    ISSN0151-1637

    Bibliographical note

    This paper is Open Access due to an agreement with the International Institute of Refrigeration (www.iifiir.org), organizer of GL2018 conference.

    Fingerprint

    Dive into the research topics of 'Comparison of a CO2 refrigeration and heat pump test system with and without ejector'. Together they form a unique fingerprint.

    Cite this