Advanced air distribution for minimizing airborne cross-infection in aircraft cabins

Arsen Krikor Melikov, Viktor Dzhartov

Research output: Contribution to journalJournal articleResearchpeer-review

Abstract

The performance of personalized ventilation combined with local exhaust at each seat was studied for the purpose of minimizing airborne cross-infection in spaces whose occupants are sedentary, such as transportation environments. Experiments were carried out in a simulated aircraft cabin section (3 rows, 21 seats). One breathing thermal manikin simulated an infected passenger as a source of pollution, and a second breathing manikin simulated an exposed passenger. The personalized ventilation supplied clean air at 6 or 10 L/s (12.7 of 21.2 cfm) from in front of each manikin's face. Air was withdrawn at a rate of 6 or 10 L/s (12.7 or (21.2 cfm) by the local exhaust system, which consisted of two exhaust terminals, one on each side of the head of the infected manikin. The cabin was ventilated with 180 L/s (381 cfm) of fresh air. Freon was mixed with the air exhaled by the infected manikin to simulate airborne pathogens. The airflow from the personalized supply outlet pushed the contaminated exhaled air backward, where it was exhausted before it had mixed with cabin air. This resulted in a substantial decrease of the tracer gas concentration in the air inhaled by the exposed manikin and in the air exhausted from the cabin.
Original languageEnglish
JournalH V A C & R Research
Volume19
Issue number8
Pages (from-to)926-933
Number of pages8
ISSN2374-4731
DOIs
Publication statusPublished - 2013