A Comparative Study on Substation Types and Network Layouts in Connection with Low-Energy District Heating Systems

Hakan Tol, Svend Svendsen

Research output: Contribution to journalJournal articleResearchpeer-review

982 Downloads (Pure)

Abstract

The study deals with low-energy district heating (DH) networks operating in low temperatures such as 55 °C in terms of supply and 25 °C in terms of return. The network layout, additional booster pumps, and different substation types such as storage tanks either equipped or not equipped in domestic hot water production site were examined. Effects of booster pumps on pipe dimensions in the latter case were investigated. Temperature drops during the summer months due to low heat demands of consumers were explored. Use of approaches such as looped networks and branched network layouts with bypasses for end-consumers were also studied, heat loss from these networks and the drop in temperature in the heat-carrier-supply medium being compared.
Original languageEnglish
JournalEnergy Conversion and Management
Volume64
Pages (from-to)551-561
ISSN0196-8904
DOIs
Publication statusPublished - 2012

Keywords

  • District heating
  • Low temperature
  • Substation Type
  • Branched network
  • Looped network
  • Booster pump

Fingerprint

Dive into the research topics of 'A Comparative Study on Substation Types and Network Layouts in Connection with Low-Energy District Heating Systems'. Together they form a unique fingerprint.