Technical assessment of electric heat boosters in low-temperature district heating based on combined heat and power analysis

Research output: Research - peer-reviewJournal article – Annual report year: 2018

View graph of relations

This paper provides a technical assessment of electric heat boosters (EHBs) in low-energy districts. The analysis is based on a hypothetical district with 23 terraced single-family houses supplied by both a lowtemperature district heating (LTDH) network and a low-voltage network (LVN). Two case studies are provided to show the active role of EHBs in a smart energy system (SES). The first case compares annual heat and power flow analyses for LTDH at five supply temperature levels, focusing on their impacts. The results show that district heating network (DHN) losses can be reduced by 35% if the supply temperature is reduced from 70 C to 50 C, but the LVN peak power will have to be increased by up to 2% using heat boosting. The second case further aggregates EHBs to provide a fuel shift (FS) service for the DHN. The results show that while LVN peak power was increased by up to 4.3%, the basic power production and peak boiler usage for DHN could be reduced by as much as 15% and 48%, respectively. In summary, lower supply temperatures and intelligent components can improve system efficiency and turn the DHN into an integrated part of a SES.
Original languageEnglish
JournalEnergy
Volume150
Pages (from-to)938-49
ISSN0360-5442
DOIs
StatePublished - 2018
CitationsWeb of Science® Times Cited: 1

    Research areas

  • Smart energy systems, 4GDH, Low-temperature district heating, Electric heat boosters, Fuel shift, Combined heat and power
Download as:
Download as PDF
Select render style:
APAAuthorCBE/CSEHarvardMLAStandardVancouverShortLong
PDF
Download as HTML
Select render style:
APAAuthorCBE/CSEHarvardMLAStandardVancouverShortLong
HTML
Download as Word
Select render style:
APAAuthorCBE/CSEHarvardMLAStandardVancouverShortLong
Word

ID: 145407642