Refrigerant mal-distribution in fin-and-tube evaporators for residential air-conditioning is investigated numerically in this paper. Essentially the influence of refrigerant mal-distribution on capacity of an evaporator is reported. In order to investigate, a model of a fin-and-tube evaporator is developed in the object-oriented modeling language Modelica. The evaporator model is a dynamic distributed one-dimensional homogeneous model, but will be used here to present results in steady state. Fin-and-tube evaporators usually have a complex circuitry, however the evaporator will be simplified to be two straight tubes. The refrigerant maldistribution is then induced to the evaporator by varying the vapor quality at the inlet to each tube and the air-flow across each tube. Finally it is shown that mal-distribution can be compensated by an intelligent distributor, that ensures equal superheat temperature in both tubes. The refrigerant is R410a.
Original languageEnglish
TitleDanske Køledage : Kompendie
Volume2009
Publication date2009
Pages25-35
StatePublished

Conference

ConferenceDanske Køledage
CityOdense Congress Center
Period01/01/09 → …

Keywords

  • mal-distribution, two-phase flow, fin-and-tube, evaporator, heat exchanger
Download as:
Download as PDF
Select render style:
APAAuthorCBEHarvardMLAStandardVancouverShortLong
PDF
Download as HTML
Select render style:
APAAuthorCBEHarvardMLAStandardVancouverShortLong
HTML
Download as Word
Select render style:
APAAuthorCBEHarvardMLAStandardVancouverShortLong
Word

Download statistics

No data available

ID: 3406699