A novel optimized LCL-filter designing method for grid connected converter

Publication: Research - peer-reviewArticle in proceedings – Annual report year: 2010

View graph of relations

This paper presents a new LCL-filters optimized designing method for grid connected voltage source converter. This method is based on the analysis of converter output voltage components and inherent relations among LCL-filter parameters. By introducing an optimizing index of equivalent total capacity of all filter components, with clear physical meaning of minimum cost and volume, a set of optimal values of attenuation ratio and inductancesplit- ratio is obtained for deciding all LCL-filter parameters. With this method, filter overall capacity can be minimized while the grid limit of switching frequency distortion is fulfilled. Compared to the existing methods, the proposed method contains only four steps without try-and-error process, so it is efficient and easy to implement. Simulation results of a 50kVA grid-connected inverter with two sets of LCL-filter parameters under different optimizing condition are presented to verify the reasonability and feasibility of the method.
Original languageEnglish
Title of host publicationIEEE PEDG 2010
PublisherIEEE Computer Society Press
Publication date2010
Pages802-805
ISBN (print)9781424456703
DOIs
StatePublished

Conference

Conference2nd International Symposium on Power Electronics for Distributed Generation Systems
Number2
CountryChina
CityHefei
Period16/06/1018/06/10
Internet addresshttp://ieeexplore.ieee.org/xpl/mostRecentIssue.jsp?punumber=5534525
CitationsWeb of Science® Times Cited: No match on DOI